THERMAL COMFORT

Human 'thermal comfort' is the state of mind that expresses satisfaction with the surrounding environment, according to ASHRAE Standard 55. Achieving thermal comfort for most occupants of buildings or other enclosures is a goal of HVAC design engineers. Indoor air quality is not part of thermal comfort, but is also a key concern of HVAC designers.
Fundamental studies of thermal comfort, such as acceptable ranges of dry-bulb temperatures, relative humidities, and activity levels were completed in the 1970s. Many of these studies, which led to the development and refinement of ASHRAE Standard 55, were performed at Kansas State University by Ole Fanger and others. Some key findings were that not everyone will be satisfied by a particular set of indoor environmental conditions, but in ranges of conditions about 80% express satisfaction. If very good conditions are in place, a maximum of 95% of all persons might be satisfied. Statistical methods were used to evaluate the thermal comfort opinions of the many test subjects to yield what are known as the ''comfort conditions''; the ''predicted mean vote'' (PMV) was one of the measures used.
Most important for thermal comfort is the so called operative temperature. This is the average of the air dry-bulb temperature and of the mean radiant temperature at the given place in a room. In addition, there should be low air velocities and no 'drafts', little variation in the radiant temperatures from different directions in the room, the humidity has to be in a comfortable range, and the air temperatures in a height of 0.1 m above the floor should not be more than 2°C lower than than the temperature at the place of the occupant's head. Also the temperatures should not change too rapidly - neither across the space nor with time.
In addition to environmental conditions, thermal comfort depends on the clothing and activity level of a person. The amount of clothing is measured against a standard amount that is roughly equivalent to a typical business suit, shirt, and undergarments. Activity level is compared to being seated quietly, such as in a classroom.
This standard amount of insulation required to keep a resting person warm in a windless room at 70 °F (21.1°C) is equal to one Clo.
Clo units can be converted to R-value by multiplying Clo by 0.88 and R-value can be converted to Clo by multiplying R-value by 1.136.

Contents
References
See also
External links

References



★ ''Thermal Comfort'', P. O. Fanger, McGraw-Hill, New York, 1970.

★ Thermal Comfort chapter, Fundamentals volume of the ''ASHRAE Handbook'', ASHRAE, Inc., Atlanta, GA, 2005.

Secrets of Warmth: For Comfort or Survival, , Hal, Weiss, Mountaineers Books, 1998,

See also



P. Ole Fanger -- died September 20, 2006

Room air distribution

Psychrometrics

Air conditioning