'Flow measurement' is the quantification of bulk
fluid or
gas movement. It can be measured in a variety of ways.
Dependent on the quantity measured different symbols are used. The
volumetric flow rate is usually given the symbol
and the
mass flow rate the symbol
.
Units of measurement
Gas
Gas volumetric flow rate is sometimes measured in "standard cubic centimeters per minute" (abbreviation sccm), a unit acceptable for use with
SI except that the additional information attached to the unit symbol. The SI standard would be m
3/s (with any appropriate prefix, with temperature and pressure specified). The term "standard" indicates that the given flow rate assumes a
standard temperature and pressure. Many other similar abbreviations are also in use, such as standard cubic feet per minute or per second.
Liquid
For liquids other units used depend on the application and industry but might include gallons (U.S. liquid or imperial) per minute, liters per second, bushels per minute and, when describing river flows, acre-feet per day.
Mechanical flow meters
There are several types of mechanical flow meter
Piston Meter
Due to the fact that they used for domestic water measurement Piston meters, (also known as Rotary Piston, or Semi-Positive displacement meters) are the most common in the UK and are used for almost all meter sizes up to and including 40 mm (1 1/2"). The piston meter operates on the principle of a piston rotating within a chamber of known volume. For each rotation, an amount of water passed through the piston chamber.
Woltmann Meter
Woltman meters, commonly referred to as Helix meters are popular at larger sizes.
Jet meters (single or Multi-Jet) are increasing in popularity in the UK at larger sizes and are commonplace in the EU.
Venturi Meter
Another method of measurement, known as a
venturi meter, is to constrict the flow in some fashion, and measure the differential pressure that results across the constriction. This method is widely used to measure flow rate in the transmission of gas through pipelines, and has been used since
Roman Empire times.
Dall Tube
A shortened form of the Venturi. Lower pressure drop than an orifice plate.
Orifice Plate
Another simple method of measurement uses an
orifice plate, which is basically a plate with a hole through it. It is placed in the flow and constricts the flow. It uses the same principle as the venturi meter in that the differential pressure relates to the velocity of the fluid flow (
Bernoulli's principle).
Pitot tube
Measurement of the pressure within a ''
pitot tube'' in the flowing fluid, or the cooling of a heated element by the passing fluid are two other methods that are used. These types of sensors are advantageous in that they are rugged, so not easily damaged in an extreme environment.
A pitot tube is an L shaped tube which is also able to measure fluid flow.
Paddle wheel
The paddle wheel translates the mechanical action of paddles rotating in the liquid flow around an axis into a user-readable rate of flow (gpm, lpm, etc.). The paddle tends to be inserted into the flow.
Pelton wheel
The Pelton wheel turbine (better described as a radial turbine) translates the mechanical action of the Pelton wheel rotating in the liquid flow around an axis into a user-readable rate of flow (gpm, lpm, etc.). The Pelton wheel tends to have all the flow travelling around it.
Turbine flow meter
The turbine flowmeter (better described as an axial turbine) translates the mechanical action of the turbine rotating in the liquid flow around an axis into a user-readable rate of flow (gpm, lpm, etc.). The turbine tends to have all the flow travelling around it.
Thermal mass flow meters
Thermal mass flow meters generally use one or more heated elements to measure the mass flow of gas. The gas temperature is also measured and compensated for. They provide a direct mass flow readout, and do not need any additional pressure temperature compensation over their specified range.
Thermal mass flow meters are used for compressed air, nitrogen, helium, argon, oxygen, natural gas. I fact, most gases can be measured as long as they are fairly clean and non-corrosive.
Vortex flowmeters
Another method of flow measurement involves placing an object (called a shedder bar) in the path of the fluid. As the fluid passes this bar, disturbances in the flow called
vortices are created. The vortices trail behind the cylinder in two rolls, alternatively from the top or the bottom of the cylinder. This vortex trail is called the
Von Kármán vortex street after von Karman's 1912 mathematical description of the phenomenon. The speed at which these vortices are created is proportional to the flow rate of the fluid. Inside the shedder bar is a
piezoelectric crystal, which produces a small, but measurable, voltage pulse every time a vortex is created. The
frequency of this voltage pulse is also proportional to the fluid flow rate, and is measured by the flowmeter electronics.
With f= SV/L
where,
� f = the frequency of the vortices
� L = the characteristic length of the bluff body
� V = the velocity of the flow over the bluff body
� S = Strouhal Number and is a constant for a given body shape
Magnetic, ultrasound and coriolis flow meters
Modern innovations in the measurement of flow rate incorporate electronic devices that can correct for varying pressure and temperature (i.e. density) conditions, non-linearities, and for the characteristics of the fluid.
Magnetic flow meters

Industrial magnetic flowmeter
The most common flow meter apart from the mechanical flow meters, is the
magnetic flow meter, commonly referred to as a "mag meter" or an "electromag". A
magnetic field is applied to the metering tube, which results in a potential difference proportional to the flow velocity perpendicular to the flux lines. The physical principle at work is
Faraday's law of
electromagnetic induction. The magnetic flow meter requires a conducting fluid, e.g. water, and an electrical insulating pipe surface, e.g. a rubber lined non magnetic steel tube.
Ultrasonic flow meters
Ultrasonic flow meters measure the difference of the transit time of ultrasonic pulses propagating in and against flow direction. This time difference is a measure for the average velocity of the fluid along the path of the ultrasonic beam. By using the absolute transit times both the averaged fluid velocity and the speed of sound can be calculated. Using the two transit times
and
and the distance between receiving and transmitting transducers
and the inclination angle
one can write the equations:
and
where
is the average velocity of the fluid along the sound path and
is the speed of sound.

Schematic view of an flow sensor.
Measurement of the
doppler shift resulting in reflecting an
ultrasonic beam off the flowing fluid is another recent innovation made possible by electronics. By passing an ultrasonic beam through the tissues, bouncing it off of a reflective plate then reversing the direction of the beam and repeating the measurement the volume of
blood flow can be estimated. The speed of transmission is affected by the movement of blood in the vessel and by comparing the time taken to complete the cycle upstream versus downstream the flow of blood through the vessel can be measured. The difference between the two speeds is a measure of true volume flow. A wide-beam sensor can also be used to measure flow independent of the cross-sectional area of the blood vessel.
Coriolis flow meters
Using the Coriolis effect that causes a laterally vibrating tube to distort, a direct measurement of mass flow can be obtained in a
coriolis flow meter. Furthermore a direct measure of the density of the fluid is obtained. Coriolis measurement can be very accurate irrespective of the type of gas or liquid that is measured; the same measurement tube can be used for
hydrogen gas and
peanut butter without re
calibration.
Laser doppler flow measurement

Laser-doppler flow meter.
Blood flow can be measured through the use of a
monochromatic laser diode. The laser probe is inserted into a tissue and turned on, where the light scatters and a small portion is reflected back to the probe. The signal is then processed to calculate flow within the tissues. There are limitations to the use of a laser doppler probe; flow within a tissue is dependent on volume illuminated, which is often assumed rather than measured and varies with the optical properties of the tissue. In addition, variations in the type and placement of the probe within identical tissues and individuals result in variations in reading. The laser doppler has the advantage of sampling a small volume of tissue, allowing for great precision, but does not necessarily represent the flow within an entire organ. The flow meter is more useful for relative rather than aboslute measurements.
See also
★
Mass flow rate
★
Volumetric flow rate
★
Gas meter
★
Water Meter
★
Orifice plate
★
Automatic Meter Reading
★
Airspeed indicator
★
Air flow meter
★
mass flow meter
★
Laser Doppler velocimetry
External links
★ '
Flowmetering' Fluid characteristics, flow theory, different meter types, instrumentation and installation practice are discussed. - Spirax Sarco
★
Thermal Flow Meter Principal of Operation
★
Clamp On Flow Meter
★
Technologies explained
★
Transonic Systems, Inc. tools for flow verification.
★
Flowmeter Directory flowmeter information.
★
EESiFlo - Concurrent Transit Time Flow Meters.
★
Overview of Vortex Flowmeters - Efunda engineering fundamentals